Caleffi 132 balancing valve with flow meter

Caleffi 132 is a balancing valve that lets you read the flow directly on its built-in flow meter and set it with a ball valve. There are 10 models: threaded brass from 1/2" to 2" and flanged cast iron from DN 65 to DN 100.

Make a quote with this seriesCompare models

Caleffi 132 balancing valve with flow meter
Function
Direct flow reading and flow setting
Body
1/2"–2": brass, insulated; DN 65–100: cast iron
Flow meter
Graduated scale, magnetically moved indicator; brass
Regulating element
Ball valve (characterised ball valve on flanged models)

Models (10)

CodeModelConnectionBodyFlow range
132402132 1/2"1/2" threadedBrass, insulated2–7 l/min
132512132 3/4"3/4" threadedBrass, insulated5–13 l/min
132522132 3/4"3/4" threadedBrass, insulated7–28 l/min
132602132 1"1" threadedBrass, insulated10–40 l/min
132702132 1 1/4"1 1/4" threadedBrass, insulated20–70 l/min
132802132 1 1/2"1 1/2" threadedBrass, insulated30–120 l/min
132902132 2"2" threadedBrass, insulated50–200 l/min
132060132 DN 65DN 65 PN 16 flangedCast iron6–24 m³/h
132080132 DN 80DN 80 PN 16 flangedCast iron8–32 m³/h
132100132 DN 100DN 100 PN 16 flangedCast iron12–48 m³/h

Series specifications

FunctionDirect flow reading and flow setting
Body1/2"–2": brass, insulated; DN 65–100: cast iron
Flow meterGraduated scale, magnetically moved indicator; brass
Regulating elementBall valve (characterised ball valve on flanged models)
Max. working pressure10 bar
Temperature range-10–110 °C
Max. glycol content50%
Technical brochureCaleffi 01149

How to choose

  • Size by the design flow of the circuit, not by pipe size: the design flow must fall within the flow range of the model.
  • There are two 3/4" options: 5–13 l/min (132512) for low-flow circuits and 7–28 l/min (132522) for higher flows.
  • For large lines use the flanged DN 65 (6–24 m³/h), DN 80 (8–32 m³/h) and DN 100 (12–48 m³/h) models; they need flat-face EN 1092-1 counter-flanges.
  • Suitable for glycol cooling and heat pump circuits with up to 50% glycol.

How to write it in a quote

Give the flow range together with the size, since one size can have different ranges: "Caleffi 132522 balancing valve with flow meter 3/4", 7–28 l/min, insulated". For flanged models add the counter-flange set as a separate line.

FAQ

What does a balancing valve with flow meter do?

It lets you read the flow through each circuit directly on the built-in flow meter, without a separate measuring instrument, and set it to the design value with the ball valve. This balances the circuits hydraulically.

How is the flow read?

The flow meter has a graduated scale and a magnetically moved indicator that shows the current flow on the scale. The setting is made by turning the ball valve.

Can it be used with glycol mixtures?

Yes, up to a maximum of 50% glycol. Working temperature is -10–110 °C and max. working pressure is 10 bar.

How do I know which model to pick?

Calculate the design flow of the circuit in l/min (threaded models) or m³/h (flanged models) and choose the model whose range contains it. If the value fits two ranges, pick the one where it sits closer to the middle.

Information compiled from the Caleffi product documents. Tekliva does not sell products or publish prices.

I want to buy

Free · no obligation

Get a price quote for this product

Your request goes to authorised Tekliva partners selling this product, and their quotes come straight to you. Usually answered within 24 hours.

Request a price quote

I sell this product

I want to quote it easily

  1. 132402 codes and technical data are ready in Tekliva
  2. Send it as a PDF or link in 30 seconds
  3. Get notified when your customer opens it; Teklobot reminds you to follow up
Prepare a quote with this productTry it without signing up: free quote generator →
Receive the requests for this product

Become a Tekliva partner and get price requests from buyers in your area.

Become a partner →